Men Under Pressure can make sure that your kitchen exhaust hood system is kept maintained and up to code.
Give Joe or Jason a call at (636) 262-8249 or (314) 568-3208 or email us at info@menunderpressureusa.com to set up an appointment or get a free quote.
The exhaust hoods in your kitchen gathers the smoke, steam, and grease and funnels it in to the areas behind your filters. Keeping this area clean is what ensures that your restaurant kitchen's exhaust system is fire safe. Scheduling regular inspections and cleanings for your kitchen exhaust and hood is the best way to ensure that your kitchen is a clean and fire safe environment.
If you would like more information on Fire Protection Services.
Below is information on what types of systems usually need hood cleaning services and what frequency these services should be performed by a licensed professional.
TABLE 8-3.1 EXHAUST CLEANING INSPECTION SCHEDULE |
||||||||||
| Type or Volume of Cooking | Frequency | |||||||||
|
||||||||||
The NFPA standard is a guideline that all fire marshalls and insurance companies follow. Listed below is the information pertaining to ventilation control and fire protection of commercial cooking operations Men Under Pressure L.L.C. follows these guidelines with no exceptions! This is for our protection as well as your own. We want to help you maintain a safe environment for your employees,patrons and business by providing you with the highest quality kitchen exhaust cleaning; along with unmatched service. We take before and after pictures of the hood, ducts and fans and e-mail them to you as soon as our work is complete so you can see that quality work has been done at your establishment.
Standards for Ventilation Control and Fire Protection of Commercial Cooking Operations, 2008 Edition |
| The National Fire Protection Association regulations are specifically designed to limit the life safety concerns and fire hazards associated with commercial cooking equipment and rooftop grease containment. |
| 7.8.2.1: The ability to drain grease out of any traps or low points formed in the fan or duct near the termination of the system into a collection container that is noncombustible, closed, rainproof, and structurally sound for the service to which it is applied and that will not sustain combustion |
| 11.6.2: Hoods, grease removal devices, fans, ducts, and other appurtenances shall be cleaned to remove combustible contaminants prior to surfaces becoming heavily contaminated with grease or oily sludge. |
| 8-3.1.1: Upon inspection, if found to be contaminated with deposits from grease-laden vapors, the entire exhaust system shall be cleaned by a properly trained, qualified, and certified company or person(s) acceptable to the authority having jurisdiction in accordance with Section 8-3. |
| 3-2.3: Grease filters shall be listed and constructed of steel or listed equivalent material and shall be of rigid construction that will not distort or crush under normal operation, handling, and cleaning conditions. Filters shall be tight fitting and firmly held in place. |
|
4-3.1: Openings shall be provided at the sides or at the top of the duct, whichever is more accessible, and at changes of direction. Openings shall be protected by approved access panels that comply with 4-3.4.4. Exception: |
| 5-1.1: Approved up blast fans with motors surrounded by the airstream shall be hinged, supplied with flexible weatherproof electrical cable and service hold-open retainers, and listed for this use. |
| 6.2.3.1: Grease filters shall be listed and constructed of steel or listed equivalent material |
| 6.2.3.2: Grease filters shall be rigid construction that will not distort or crush under normal operation, handling, and cleaning conditions. |
| 6.2.3.3: Grease filters shall be arranged so that all exhaust air passes through the grease filters. |
| 7.3.1: Openings shall be provided at the sides or at the top of the duct, whichever is more accessible, and at changes of direction. |
| 7.4.1.3: Openings on horizontal grease duct systems shall be provided with safe access and a work platform when not easily accessible from a 3 m (10 ft) stepladder. |
| 8.1.1.1: Approved up blast fans with motors surrounded by the airstream shall be hinged, supplied with flexible weatherproof electrical cable and service hold-open retainers, and listed for this use. |
| 8.1.5.3.1: Up blast fans shall be supplied with an access opening of a minimum 76 mm by 127 mm (3 in. by 5 in.) or a circular diameter of 101 mm (4 in.) on the curvature of the outer fan housing to allow for cleaning and inspection of the fan blades. |
| 11.6.10: When an access panel is removed, a service company label or tag preprinted with the name of the company and giving the date of inspection or cleaning shall be affixed near the affected access panels. |
|
** Reproduced with permission from NFPA® 96: Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations, Copyright© 2008, National Fire Protection Association. This reprinted material is not the complete and official position of the NFPA on the referenced subject, which is represented only by the standard in its entirety. |